Welcome to building.co.uk. This site uses cookies. Read our policy.

Table 1: Comparison of energy consumption for groundwater cooling scheme
 Groundwater cooling systemsVapour compression refrigeration
Cooling required100 kW for 1 hour100 kW for 1 hour
Cooling energy output100 kWh100 kWh
Dt for groundwater5 °CN/a
Cp for water4.2 kJ/kg °CN/a
Mass of groundwater needed17133 kgN/a
Volume of groundwater needed1000 m3N/a
Cost of spentwater17.1 @ 1.135p/m3 %3D £0.19N/a
COSP of cooling system402
Energy consumption kWh100/40%3D2.5100/3 %3D 33.3
Energy cost@£0.082/kWh2.5 x 0.0082* %3D £0.20533.3 x 0.082* %3D £2.73
Total cost£0.395£2.73
CO2 emissions assuming 0.43 kg CO2/kWh1.1 kg CO214.3 kg CO2
*from http://www.dti.gov.uk/energy/statistics/publication/prices
Table 2: Heating comparison for different technologies
 New boiler (condensing)Air source heat pumpGround source heat pump
Heating load100 kWh100 kWh100 kWh
Seasonal efficiency88% from www.sedbuck.co.uk300% SPF from Hundy, 2004%2400% SPF from IEA, 1995
Energy input (kWh)113.63325
Cost of energy p/kWh3.1 p8.2 p8.2 p
Cost of input energy ££3.52£2.71£2.05
CO2 emitted21.6 kg14.2 kg10.75 kg
Table 3: Cooling comparison for different technologies
 Air source heat pumpGround source heat pump
Cooling load100 kWh100 kWh
Seasonal efficiency280% SPF320 % SPF
Energy input (kWh)35.731.25
Cost of energy p/kWh8.2 p8.2 p
Cost of input energy ££2.93£2.56
CO2 emitted15.3 kg13.2 kg