Potential implications of the amendments of Approved Document B on the cost of the services
Building typeAmendmentIndicative cost
1 & 2 Blocks of flatsProvision of ventilation systems for the smoke control of common escape routes;Based on a 10-floor development
 Natural ventilation system comprising automatically opening vents £2000 per floor per core
 Or mechanically pressurised system£8000 per floor per core
3 Blocks of flatsProvide sprinkler protection to blocks of flats over 30 m high (to flats only, not common areas)£17-23/m2 on the GIA
  Depends on the building height and the need for intermediate pumps and tank
4 Residential care homesProvision of free swing closing devices on bedroom doors (based on one bed per bedroom)£150-200/door
 Or provision of sprinkler protection in residential care homes with more than one bed per bedroom£15/m2 on the GIA
5 Offices, shop and commercial, assembly and recreationInclude for: Warning people with impaired hearing, Emergency voice communication to allow evacuation of people waiting in refugesThis brings the document in line with other regulations, so on the basis that these are being provided, it is assumed there is no additional cost
6 Assembly and recreationProvide for fire-fighting shafts in buildings between 7.5-18 m in height (fire-fighting lifts not required in shafts) 
 Dry riser£1500 per landing per core
 Natural ventilation system comprising a system of automatically opening vents £2000 per floor per core
 Or mechanically pressurised system£8000 per floor per core
7 StorageRemove provision for fire-fighting shafts in buildings between 7.5-18 m in height (assume no fire-fighting lifts in shafts) 
 Omit dry riser£1500 per landing per core
 Omit natural ventilation system comprising a system of automatically opening vents£2000 per floor per core
 Or omit mechanically pressurised system£8000 per floor per core
8 Industrial/StorageA maximum unsprinklered compartment size for a single-storey warehouse of 20,000 m² and/or 18 m high£25-40/m2 for sprinkler system
  Depends on whether racking protection is required
9 Self storageA maximum unsprinklered compartment size of 2000 m²£25-35/m² for sprinkler system
  Depends on degree of cellurisation
10 All buildings other than dwelling housesDiscount an escape stair in buildings over 45 m with phased evacuation. Allowance for additional stair; 
 Mechanical stair pressurisation ventilation system£8000 per floor per core
 Assume wet riser£2000-4500 per landing per core
  Depends on the building height and the need for intermediate pumps, tank and valving
11 All building other than dwelling housesProvision of rising mains in escape stairs in all unsprinklered buildings over 30m tall in order to meet maximum distances from a fire main outlet 
 Dry riser£1500 per landing per core
12 All buildingsProvision of cavity barriers in floor voidsThis brings the document in line with other regulations so on the basis that these are being provided, it is assumed there is no additional cost