Keep up to dateHow to specify a condensing boiler in a typical installation with a 240 kW load | ||||
Cascade of three wall-hung condensing boilers | Floor-standing compact condensing boiler | Floor-standing condensing boiler | Cast iron with stainless steel condensing heat exchanger | |
Buderus example | GB162 3 x 80 kW | GB312 240 kW | SB615 240kW | GE315 PLUS 260 kW |
Efficiency | Up to 110% NCV ** | Up to 108% NCV ** | Up to 109% NCV ** | Up to 107% NCV ** |
Built in back-up if one boiler is not in operation | ** | |||
Ease of transportation into the heating room | Weight of each unit only 70 kg ** | Only 60 mm wide with transport frame ** | Assembly in heating room * | |
Installation space | Up to 400 kW in 1 m² ** | ** | * | |
Integration into existing large-volume heating systems | Recommend installation with low-loss header and strainer * | Recommend installation with low-loss header and strainer * | ** | ** |
Maximum system pressure | 400 kPa required. For larger pressures, install with separated plate head * | 400 kPa required. For larger pressures, install with separated plate head * | 500 kPa ** | 600 kPa ** |
Modulation range | Down to 19 kW ** | Down to 66 kW ** | About 70 kW depending on type of pressure jet burner * | About 70 kW depending type of pressure jet burner * |
Noise level | Whisper quiet 55 dB(A) * | Whisper quiet 55 dB(A) * | Depends on type of pressure jet burner chosen. Normally 60-70 db(A). Use of burner hood can reduce noise level * | Depends on type of pressure jet burner chosen. Normally 60-70 db(A). Use of burner hood can reduce noise level * |
Weight suitable for rooftop installation | ** | ** | ||
Maximising efficiency of systems with high and low-temperature heating circuits | Separate connections for low and high-temperature returns as standard ** | Two return connections on the condensing heat exchanger ** | ||
Summary | Everyone’s favourite. Can be adapted to any system but must have low-loss header and the heating circuits must be balanced. Where the heating system is old or high system pressure is required, separate from the system with a plate heat exchanger | Similar to the cascade of wall-hung boilers, but because it is a single boiler, total installation costs are lower. However, you do not have the back-up cover of the cascade | The best for big systems of high water content, especially old heating systems. However, you need to have good access | The problem solver. For systems with high water content, especially old heating systems where access is difficult |
* Good solution for this type of installation | ||||
** Excellent solution for this type of installation |