How to specify a condensing boiler in a typical installation with a 240 kW load
 Cascade of three wall-hung condensing boilers Floor-standing compact condensing boiler Floor-standing condensing boilerCast iron with stainless steel condensing heat exchanger
Buderus example GB162 3 x 80 kW GB312 240 kW SB615 240kW GE315 PLUS 260 kW
Efficiency Up to 110% NCV ** Up to 108% NCV ** Up to 109% NCV ** Up to 107% NCV **
Built in back-up if one boiler is not in operation **   
Ease of transportation into the heating room Weight of each unit only 70 kg ** Only 60 mm wide with transport frame **  Assembly in heating room *
Installation space Up to 400 kW in 1 m² ** *** 
Integration into existing large-volume heating systems Recommend installation with low-loss header and strainer *Recommend installation with low-loss header and strainer *****
Maximum system pressure 400 kPa required. For larger pressures, install with separated plate head *400 kPa required. For larger pressures, install with separated plate head *500 kPa ** 600 kPa **
Modulation rangeDown to 19 kW ** Down to 66 kW ** About 70 kW depending on type of pressure jet burner * About 70 kW depending type of pressure jet burner *
Noise level Whisper quiet 55 dB(A) * Whisper quiet 55 dB(A) * Depends on type of pressure jet burner chosen. Normally 60-70 db(A). Use of burner hood can reduce noise level * Depends on type of pressure jet burner chosen. Normally 60-70 db(A). Use of burner hood can reduce noise level *
Weight suitable for rooftop installation** **  
Maximising efficiency of systems with high and low-temperature heating circuits   Separate connections for low and high-temperature returns as standard **Two return connections on the condensing heat exchanger **
Summary Everyone’s favourite. Can be adapted to any system but must have low-loss header and the heating circuits must be balanced. Where the heating system is old or high system pressure is required, separate from the system with a plate heat exchangerSimilar to the cascade of wall-hung boilers, but because it is a single boiler, total installation costs are lower. However, you do not have the back-up cover of the cascadeThe best for big systems of high water content, especially old heating systems. However, you need to have good accessThe problem solver. For systems with high water content, especially old heating systems where access is difficult
* Good solution for this type of installation
** Excellent solution for this type of installation