Welcome to building.co.uk. This site uses cookies. Read our policy.

Table 1: The implications of LV or HV metering
LV meteringHV metering
  • REC owns and maintains 11 kV intake switchgear and transformers
  • Client owns and maintains 11 kV distribution switchgear and transformers
  • REC controls access to substation(s)
  • Client controls access to distribution substations
  • Metering after transformer, losses not metered
  • Metered before transformer, losses paid for by client
  • Maximum transformer size 1000 kVA, but may have more than one
  • Transformer rating and number determined by m&e consultant
  • Transformers invariably oil-filled indoor or outdoor
  • Transformers almost invariably cast resin type for indoor substations