Keep up to dateTable 1: Number of systems monitored by system type and refrigeration cycle | |||
System Type | Cooling only | Reverse cycle | Total |
All-air (vav and constant volume) systems. | 7 | 0 | 7 |
Fancoil (two-pipe and four-pipe) | 5 | 1 | 6 |
Chilled ceilings (passive and active, beams and panels) | 4 | 1 | 5 |
DX split (single and multiples) | 6 | 3 | 9 |
DX vrf (three-pipe heat recovery) | 0 | 4 | 4 |
Unitary heat pump | 1 | 0 | 1 |
Total | 23 | 9 | 32 |
Table 2: Average annual run-hours by system type | ||
System type | Cooling only (hours) | Reverse cycle (hours) |
All-air | 4904 | n/a |
Fancoils | 4686 | 7073 |
Chilled ceilings | 3180 | 5308 |
DX split | 6560 | 4136 |
DX vrf | n/a | 6960 |
All | 4919 | 5848 |
Table 3: Comparison of calculated internal gains to composite guidance values | ||
Load type | Calculated values (W/m2 treated floor area) | Composite guidance (W/m2) |
Occupancy | 6 to 30 | 20 |
Lighting | 6 to 34 | 8 to 32 |
Small power | 6 to 34 | 7 to 45 |
Total internal gains | 21 to 86 | 37 to 90 |