Table 1: Number of systems monitored by system type and refrigeration cycle
System TypeCooling onlyReverse cycleTotal
All-air (vav and constant volume) systems.707
Fancoil (two-pipe and four-pipe)516
Chilled ceilings (passive and active, beams and panels)415
DX split (single and multiples)639
DX vrf (three-pipe heat recovery)044
Unitary heat pump101
Total23932
Table 2: Average annual run-hours by system type
System typeCooling only (hours)Reverse cycle (hours)
All-air4904n/a
Fancoils46867073
Chilled ceilings31805308
DX split65604136
DX vrfn/a6960
All49195848
Table 3: Comparison of calculated internal gains to composite guidance values
Load typeCalculated values (W/m2 treated floor area)Composite guidance (W/m2)
Occupancy6 to 3020
Lighting6 to 348 to 32
Small power6 to 347 to 45
Total internal gains21 to 8637 to 90