Keep up to dateTable 1: Work that need not be notified to building control bodies |
Work consisting of: |
Replacing accessories such as socket-outlets, control switches and ceiling roses |
Replacing the cable for a single circuit only, where damaged, for example, by fire, rodent or impact (a) |
Re-fixing or replacing the enclosures of existing installation components (b) |
Providing mechanical protection to existing fixed installations (c) |
Work that is not in a kitchen or special location and does not involve a special installation (d) and consists of: |
Adding lighting points (light fittings and switches) to an existing circuit (e) |
Adding socket-outlets and fused spurs to an existing ring or radial circuit (e) |
Installing or upgrading main or supplementary equipotential bonding (f) |
Notes |
(a) On condition that the replacement cable has the same current carrying capacity, follows the same route and does not serve more than one sub-circuit through a distribution board |
(b) If the circuit’s protective measures are unaffected |
(c) If the circuit’s protective measures and current-carrying capacity of conductors are unaffected by increased thermal insulation |
(d) Special locations and installations are listed in Table 2 |
(e) Only if the existing circuit protective device is suitable and provides protection for the modified circuit, and other safety provisions are satisfactory |
(f) Such work shall comply with other applicable legislation, such as the Gas Safety (Installation and Use) Regulations |
Table 2: Special locations and installations (a) |
Locations containing a bath tub or shower basin |
Swimming pools or paddling pools |
Hot air saunas |
Electric floor or ceiling heating systems |
Garden lighting or power installations |
Solar photovoltaic (PV) power supply systems |
Small-scale generators such as micro-CHP units |
Extra-low voltage lighting installations, other than pre-assembled, CE-marked lighting sets |
Notes |
See IEE Guidance Note 7 which gives more guidance on achieving safe installations where risks to people are greater |