Keep up to dateTable 1: Functions of flow control devices compared | ||||||
Flow control device | Isolation | Manual flow regulation | Automatic flow regulation | Pressure regulation | Flow measurement | System self balancing |
Pressure independent flow control valve | Yes | Yes | Yes | Yes | Yes | Yes |
Isolating Valve | Yes | No | No | No | No | No |
Regulating valve | Yes | Yes | No | No | No | No |
Double regulating | Yes | Yes | No | No | No | No |
Venturi-nozzle | No | No | No | No | Yes | No |
Fixed-orifice fitting | No | No | No | No | Yes | No |
Fixed-orifice/double regulating coupled | Yes | Yes | No | No | Yes | No |
Constant flow controller | No | No | Yes | No | No | No |
Variable-orifice valve | Yes | Yes | No | No | Yes | No |
Differential-Pressure control valve | No | No | Yes | Yes | No | No |
Auto flow controller | No | No | Yes | No | No | No |