Welcome to building.co.uk. This site uses cookies. Read our policy.

How Ludgate House could get a C
  kg CO² per m² floor area  
  HeatingCoolingAuxiliaryLightingHot waterTotalRating
 Notional building7.823.216.521.02.871.3100%C
1Ludgate House – base case25.541.227.220.42.0116.3162%E
2Improving U-value of glazing from 4 to 2.820.944.327.220.42.0114.8160%E
3Boiler efficiency improved from 0.65 to 0.718.644.327.220.41.8112.3156%E
4Wall U-value improved from 0.6 to 0.5518.144.427.220.41.8111.9156%E
5Air permeability from 10 to 5 m3/h/m212.044.727.220.41.8106.1147%E
6System air-leakage tests passed10.338.623.120.41.894.1131%D
7System energy metering with alarms9.936.622.020.41.890.7126%D
8Lighting improved to HF triphosphor10.434.422.016.01.884.6118%D
9Use of air-extracting luminaires10.533.622.016.01.883.9117%D
10Cooling efficiency improved from 2.5 to 310.522.422.016.01.872.7101%C
11Specific fan power improved from 3 to 210.921.116.816.01.866.693%C